Furrow Pump, Inc.


Furrow Pump


HomeContent IndexPump SelectorProductsApplicationsTroubleshootingemailResourcesButtoneditorial.jpg (2523 bytes)Buttonnewsletter.jpg (2193 bytes)Site Map


Furrow Pump, Inc.

P.O. Box 1849

8525 SW St. Helens Dr.

Wilsonville, OR 97070

Phone: (800) 937-3666

FAX: (800) 377-9960

www.furrowpump.com


TitleNewsletterExample.jpg (7537 bytes)

Example 2:  The Rest of the Story
A local tool manufacturer uses acid to clean and prepare the surfaces of its components, and caustic cleaner for its tanks and other maintenance purposes.  Along with their process and cooling water, their water flows can vary from zero to 500 gallons per minute.   As much as possible, acid and caustic dumps are planned and done at the same time so that they neutralize each other, minimizing the amount of pH treatment chemical needed to keep the plant discharge pH within the allowed window of 5 to 10.  Still, it is difficult to always do this, so the wastewater pH can vary from as low as 3 to as high as 11, so a treatment system was called for to insure that the plant effluent always complies with environmental standards.
There is of course no need to treat water within the acceptable discharge range, but when sudden surges of acid or caustic are detected by the pH probe, the system must respond instantly, and it must respond in proportion to that moment's flow to get the treatment right.  This is possible due to the plant's effluent flowmeter, which has a 4 to 20 mA output signal.   With the chemical pumps connected directly to this control signal, they are ready to respond immediately at the appropriate level whenever the pH goes beyond its programmed set points.  For this application, having those set points at 6 and 9 should prevent the discharge from going below 5 or above 10. This does depend on adequate mixing and reaction time, of course, which need to be engineered into the system.
The system described here works by controlling power to the pumps in relation to the measured pH load.   Essentially, the pumps are "asleep" inside the 5 to 10 discharge window, because they have no 120 VAC power to operate with.  The flow signal might be telling one of the pumps to go like mad, but with a neutral pH there is no need to treat the water, and they can't work without power.  But as soon as the pH wanders, a relay turns on the power and the pump responds in proportion to the demand.  All in all, this is a pretty efficient way to operate.  The only time water that could use treatment doesn't get treated, is when it is below the minimum measurable flow (which is neutralized by the bulk of the water already in the system).  The tool manufacturer gets an efficient and economical package to solve his discharge problem.